Resistive Loadbanks |
|
| |


Back
|
|
Why Crestchic resistive loadbanks?
- Delivered with your choice from our wide range
of alternative control systems allowing you to operate local or
remote, manual or automatic
- Variable load with 1kW resolution is provided
by totally enclosed fan-cooled tubular stainless steel resistor
elements switched by contactors
- A wide range of sizes
- Designed to operate at 3 phase, 50 or 60 Hz;
with single phase options available
- Rated for continuous operation in ambient temperatures
up to 50ºC
- Supplied in either folded sheet steel enclosures
or ISO type containers - both providing Control \ Electrical Area
IP55 Load \ Element Section IP0 protection suitable for outdoor
use. Hot exhaust at grilles.
- Available in two styles - one designed for
fixed installation at a permanent outdoor location, the other
easily transportable for moving from site to site
- Fitted with lifting facilities for easy handling
- Transportable loadbanks can be fitted with
heavy duty castor wheels or road trailers for greater manoeuvrability
- Loadbanks in ISO type container enclosures
have forklift pockets and twist lock corners for easy handling
- Built in the UK to a high industrial standard,
all manufacturing processes are BS EN ISO 9001 - 2000
- Option of Load bank attenuation if required.
|
|
| |
| LOADBANK FRAMESIZE DATASHEET |
| Type |
Transportable |
Fixed |
Typical to Both |
| - |
Dimensions (mm) |
Weight (kg) |
| Frame |
Max kW |
Length |
Height |
Length |
Height |
Width |
- |
| A |
10 |
550 |
415 |
550 |
400 |
475 |
25 |
| B |
30 |
825 |
515 |
825 |
500 |
500 |
52 |
| C |
100 |
750 |
730 |
845 |
675 |
875 |
130 |
| D |
300 |
865 |
1350 |
1000 |
1275 |
875 |
250 |
| E |
400 |
1300 |
1525 |
1450 |
1475 |
1025 |
390 |
| F |
700 |
1575 |
1525 |
1750 |
1450 |
1000 |
650 |
| G |
1200 |
2060 |
2200 |
2535 |
2150 |
1000 |
1340 |
| H |
1600 |
N/A |
N/A |
3100 |
2152 |
1000 |
1550 |
| I |
2600 |
2991 |
2430 |
2991 |
2430 |
2590 |
5100 |
| J |
3500 |
6058 |
2430 |
6058 |
2430 |
2590 |
6400 |
Elements are fan cooled with horizontal
airflow on frame sizes A to F, vertical airflow on G to J.
|
|
| |
For further information on the products
available, please contact the Crestchic sales team direct. Email
sales@crestchic.co.uk
Back
|
|
|